Below is a copy of the report that may be printed out to include in your proposal or submitted to obtain a permit
|
Company |
Acme |
|
Customer |
James Brown |
|
Preparer |
J White |
|
Address |
5735 Shady Lane, Anytown, Earth |
|
Phone |
252-555-1028 |
|
|
|
|
Date |
10/25/09 |
|
|
|
|
|
|
|
Phone |
555-555-5555 |
1. Design Conditions
|
|
Indoor |
Outdoor |
Temp. Diff. |
|
Winter |
70 |
20 |
50 |
|
Summer |
75 |
95 |
20 |
2. How would you describe the summer humidity in your area? Moderately Humid 40
3. Volume of building (cubic feet) 23112
4. How tight is the house? Average-over 1500 Sq. Ft. 0
5. Number of occupants 5
6. Overhang Characteristics (this section optional)
|
|
East |
West |
South |
|
Distance of overhang |
|
|
|
|
from top of window (Ft.) |
0.5 |
0.5 |
0 |
|
Length of overhang |
1.5 |
1.5 |
0 |
7. Solar gain through glasses
|
Facing |
Total area |
Type of glass/HTM |
Linear ft. |
Unshaded |
Shaded |
BTUH |
|
|
N/Shaded |
56 |
Single |
32 |
below OH |
|
56 |
|
|
South |
0 |
Single |
50 |
0 |
0 |
0 |
0 |
|
East |
64 |
Single |
90 |
15 |
53 |
10 |
4794 |
|
West |
69 |
Single |
90 |
15 |
58 |
10 |
5244 |
|
|
|
|
|
Total North and Shaded |
77 |
2478 |
|
|
Skylight |
0 |
clear |
150 |
|
|
|
0 |
|
|
|
|
|
Total solar gain |
|
12517 |
|
|
Adjust for tinted or reflective window coating |
NO |
1 |
12517 |
||||
8. Ducts
Location Enclosed in unconditioned space 0.7
Insulation R-4 0.15
Duct Loss/Gain 0.105
9. Load Calculation
|
Elements of Load |
Insulation |
Area/lin.ft. |
U-value |
BTUH Loss |
BTUH Gain |
|
Gross Wall |
|
2196 |
Glass Solar Gain |
12517 |
|
|
Glass 1 |
Double |
189 |
0.6 |
5670 |
|
|
Glass 2 |
Single |
0 |
1 |
0 |
|
|
Skylights |
Single glass |
0 |
1.2 |
0 |
|
|
Doors |
Insulated or Storm |
43 |
0.4 |
860 |
344 |
|
Net walls |
R-11 |
1964 |
0.08 |
7856 |
3142.4 |
|
Ceilings |
R-19 |
2568 |
0.055 |
7062 |
6355.8 |
|
Floors |
NO INSULATION |
0 |
0.15 |
0 |
0 |
|
Open Floors |
NO INSULATION |
0 |
0.31 |
0 |
0 |
|
Slab Floors |
1" INSULATION, R-5 |
244 |
0.45 |
5490 |
2196 |
|
|
|
Infiltration |
14830.2 |
5932.08 |
|
|
|
|
People |
|
1500 |
|
|
|
|
Appliances |
|
1800 |
|
|
|
|
Sub total |
41768.199 |
33788.18 |
|
|
|
|
Ducts |
4385.661 |
3547.759 |
|
|
|
|
Sub total |
46153.859 |
37335.938 |
|
|
|
|
Latent load |
|
7334.208 |
|
|
|
|
TOTAL BTUH |
46153.859 |
44670.145 |
|
Basement Calculation
|
Elements of Load |
Insulation |
Area/lin.ft. |
U-value |
BTUH Loss |
BTUH Gain |
|
Walls above grade |
|
0 |
|
||
|
Glass |
|
0 |
0 |
0 |
|
|
North |
|
0 |
0 |
|
0 |
|
South |
|
0 |
0 |
|
0 |
|
East |
|
0 |
0 |
|
0 |
|
West |
|
0 |
0 |
|
0 |
|
Doors |
|
0 |
0 |
0 |
0 |
|
Net walls above |
|
0 |
0 |
0 |
0 |
|
Walls below grade |
|
0 |
0 |
0 |
0 |
|
Ceilings |
|
0 |
0 |
0 |
0 |
|
Floors |
|
0 |
0.024 |
0 |
0 |
|
Infiltration |
|
0 |
|
0 |
0 |
|
Number of people |
0 |
300 |
|
0 |
|
|
|
|
Appliances |
|
0 |
|
|
|
|
Sub total |
0 |
0 |
|
|
|
|
Latent load |
|
0 |
|
|
|
|
Total BTUH |
0 |
0 |
|
|
Total whole house load including basement |
46153.859 |
44670.145 |
|||
Energy Cost Analysis
Heat Loss 46153.859 Heating degree days (from map) 3300
Heat Gain 44670.145 Cooling degree days (from map) 1700
Summer Design Temp. 95 Summer Design Temp. Diff. 20
Winter Design Temp. 20 Winter Design Temp. Diff. 50
System #1 (less efficient)
|
|
|
Efficiency |
Fuel Cost |
Price |
|
Air Conditioning |
|
13 |
0.11 |
$514.05 |
|
Heating |
NATURAL GAS |
0.8 |
1.25 |
$1142.308 |
|
|
Total annual operating cost of system 1 |
$1656 |
||
System #2 (more efficient)
|
|
|
Efficiency |
Fuel Cost |
Price |
|
Air Conditioning |
|
15 |
0.11 |
$445.51 |
|
Heating |
NATURAL GAS |
0.92 |
1.25 |
$993.311 |
|
|
Total annual operating cost of system 2 |
$1438 |
||
|
Cost of new or more efficient system |
$7950 |
|
Cost of less efficient system |
$9756 |
|
Additional investment |
$1806 |
|
Yearly savings |
$217 |
|
Payback (years) |
8.3 |
|
Return on Investment (ROI) |
12% |
|
Total Heat Loss |
41927.344 |
|
Total Heat Gain |
41201.234 |
|
System CFM |
1600 |
|
Room name |
Kitchen |
utility room |
den/dining |
m bath |
M BR |
Bath 2 |
BR 2 |
BR 3 |
|
Gross Wall |
270 |
288 |
207 |
63 |
270 |
72 |
252 |
162 |
|
North Windows |
10 |
0 |
12 |
0 |
12 |
9 |
12 |
0 |
|
South Windows |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
|
East Windows |
19 |
0 |
24 |
9 |
12 |
0 |
0 |
0 |
|
West Windows |
0 |
0 |
0 |
0 |
0 |
0 |
12 |
24 |
|
Doors |
22 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
|
Net Walls |
219 |
288 |
171 |
54 |
246 |
63 |
228 |
138 |
|
Ceiling |
210 |
126 |
634 |
98 |
224 |
72 |
196 |
252 |
|
Floor-crawl |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
|
Floor-open |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
|
Floor-slab |
30 |
32 |
23 |
7 |
30 |
7 |
28 |
18 |
|
Volume |
1890 |
1134 |
5706 |
882 |
2016 |
648 |
1764 |
2268 |
|
People |
1 |
0 |
1 |
0 |
1 |
0 |
1 |
1 |
|
Appliance |
1200 |
0 |
600 |
0 |
0 |
0 |
0 |
0 |
|
Duct Loss |
488 |
309 |
807 |
155 |
450 |
135 |
412 |
401 |
|
Duct Gain |
531 |
111 |
708 |
143 |
339 |
76 |
321 |
408 |
|
Latent |
599.76 |
359.856 |
1810.704 |
279.888 |
639.744 |
205.632 |
559.776 |
719.712 |
|
Heat Loss |
5139 |
3255 |
8493 |
1634 |
4738 |
1429 |
4345 |
4226 |
|
Heat Gain |
6192 |
1535 |
9270 |
1788 |
4208 |
1015 |
3948 |
5014 |
|
Cooling CFM |
240 |
59 |
360 |
69 |
163 |
39 |
153 |
194 |
|
Heating CFM |
196 |
124 |
324 |
62 |
180 |
54 |
165 |
161 |
|
Room name |
foyer |
liv room |
|
|
|
|
|
|
|
Gross Wall |
72 |
324 |
|
|
|
|
|
|
|
North Windows |
0 |
0 |
|
|
|
|
|
|
|
South Windows |
0 |
0 |
|
|
|
|
|
|
|
East Windows |
0 |
0 |
|
|
|
|
|
|
|
West Windows |
7 |
32 |
|
|
|
|
|
|
|
Doors |
42 |
0 |
|
|
|
|
|
|
|
Net Walls |
23 |
292 |
|
|
|
|
|
|
|
Ceiling |
112 |
308 |
|
|
|
|
|
|
|
Floor-crawl |
0 |
0 |
|
|
|
|
|
|
|
Floor-open |
0 |
0 |
|
|
|
|
|
|
|
Floor-slab |
8 |
36 |
|
|
|
|
|
|
|
Volume |
1008 |
2772 |
|
|
|
|
|
|
|
People |
0 |
0 |
|
|
|
|
|
|
|
Appliance |
0 |
0 |
|
|
|
|
|
|
|
Duct Loss |
239 |
584 |
|
|
|
|
|
|
|
Duct Gain |
161 |
506 |
|
|
|
|
|
|
|
Latent |
319.872 |
879.648 |
|
|
|
|
|
|
|
Heat Loss |
2515 |
6147 |
|
|
|
|
|
|
|
Heat Gain |
2020 |
6206 |
|
|
|
|
|
|
|
Cooling CFM |
78 |
241 |
|
|
|
|
|
|
|
Heating CFM |
96 |
234 |
|
|
|
|
|
|